Phone.: (03) 9311 7822 | sales@liquipvictoria.com.au

Categories

FG Series - VF-21SB-22SB Monitor Cartridges - Outside/Inside Flow

The Facet Fuel-Gard® monitor cartridges meet the effluent requirements of the EI specification 1583 — Laboratory test and minimum performance levels for aviation fuel monitors.

The cartridge is made up of layered and pleated, multi-media sections with inner support shells and an outer wrap.

A special water absorbent media retains water and the pleats expand. As the maximum water holding capacity is reached, a reduction in flow occurs, indicating the cartridge should be changed. Maximum recommended operating temperature is 160 °F (71 ºC).

  • Tested to meet effluent requirements of EI 1583 latest edition
  • Multi-layered media for increased solids holding, water removal and shutdown protection
  • Not adversely affected by exposure to temperatures varying from -65 °F to 160 °F (-54 ºC to 71 ºC)
  • suits VF-21SB/22SB monitor vessels.

Flow direction
Outside to in.

Materials 
Carbon steel structural components
Heavy duty metal center tube and outer shell for extra structural strength
All metal components coated to protect against corrosion
Standard gaskets are Buna-N—other materials available on request

WARNING: MONITOR CARTRIDGES SHOULD NEVER BE USED WITH FUELS CONTAINING ANTI-ICING ADDITIVES SUCH AS FSII, PRIST AND DI-EGME. THIS INCLUDES PRE-MIXED AND MILITARY FUELS CONTAINING THESE ADDITIVES. THE USE OF MONITOR CARTRIDGES WITH FUELS CONTAINING ANTI-ICING ADDITIVES MAY RESULT IN (1) A FAILURE OF THE MONITOR CARTRIDGE AND/OR (2) MIGRATION OF FILTRATION MEDIA INTO THE FUEL STREAM, EITHER OF WHICH COULD POTENTIALLY CAUSE DAMAGE TO OR SUDDEN FAILURE OF THE CORRESPONDING ENGINE. THE SUPPLIER SHALL NOT BE LIABLE IN ANY RESPECT FOR ANY DAMAGE OR LOSS THAT ARISES FROM THE USE OF MONITOR CARTRIDGES WITH FUELS CONTAINING ANTI-ICING ADDITIVES. SUCH USE IS ENTIRELY AT THE USER’S RISK.

Item Outside Diameter Nominal Length Shipping Weight Jet Fuel Av-Gas
  Initial DP Flow Initial DP Flow
  in mm in mm lbs kg psi kPa gpm lpm psi kPa gpm lpm
21 Series
FG-O-609-7 6 152 9 230 4 1.8 3.5 24.1 36 136 2.5 17.2 36 136
22 Series
FG-O-612-7 6 152 12 300 6 2.7 5.5 37.9 48 182 3.5 24.1 48 182

* For applications other than AV-Gas and Jet Fuel, please contact the nearest Facet office.

**DP given for viscosity <2 cSt

 